The store will not work correctly in the case when cookies are disabled.
ACV Heatmaster 35TC Condensing Boiler 05652201
Overview
ACV Heatmaster 35TC Gas Fired Condensing Combination Unit 5652201
HeatMaster 35 TC
Combined gas fired condensing boiler and water heater with stainless steel heat exchanger.
- 10-Year Heat Exchanger Warranty
- Tank-in-Tank
- BIM Objects
- Nat Gas and LPG
- Domestic and Commercial
- GAS
- BOILERS
- DHW PRODUCTION
- STANDARD
- CONCENTRIC
- FLOOR INSTALLATION
# GTIN : 5400891001462
# P/N : 05652201
ACV Heatmaster 35TC Gas Fired Condensing Combination Unit 5652201
|
HeatMaster 25 TC |
HeatMaster 35 TC |
HeatMaster 45 TC |
HeatMaster 70 TC |
HeatMaster 85 TC |
HeatMaster 120 TC |
Capacity (total) |
L |
196 |
196 |
196 |
315 |
315 |
315 |
Capacity (primary) |
L |
100 |
100 |
100 |
125 |
125 |
125 |
Capacity (domestic hot water) |
L |
96 |
96 |
96 |
190 |
190 |
190 |
Capacity expansion tank(s) |
L |
- |
- |
- |
- |
- |
- |
Chimney: Max pressure drop in flue pipe |
Pa |
130 |
130 |
130 |
150 |
150 |
170 |
Chimney: max length of concentric flue pipe |
m |
20 |
20 |
20 |
22 |
22 |
21 |
Chimney connection |
Ømm |
80/125 |
80/125 |
80/125 |
100/150 |
100/150 |
100/150 |
Connection - heating |
Ø" |
1 F |
1 F |
1 F |
1 ½ F |
1 ½ F |
1 ½ F |
Connection - DHW |
Ø" |
1 M |
1 M |
1 M |
1 M |
1 M |
1 M |
Connection gas |
Ø" |
3/4 M |
3/4 M |
3/4 M |
3/4 M |
3/4 M |
3/4 M |
Connection - safety valve |
Ø" |
1/2M |
1/2M |
1/2M |
1/2 M |
1/2 M |
1/2 M |
Max operating temperature |
°C |
87 |
87 |
87 |
87 |
87 |
87 |
Water pressure drop boiler at Δt = 20°C |
mbar |
3 |
6 |
10 |
9 |
14 |
27 |
Max service pressure heating (primary) |
bar |
3 |
3 |
3 |
3 |
3 |
3 |
Max service pressure (DHW) |
bar |
8,6 |
8,6 |
8,6 |
8,6 |
8,6 |
8,6 |
Height when tilted |
mm |
1855 |
1855 |
1855 |
2277 |
2277 |
2277 |
Weight (empty) |
kg |
177 |
177 |
177 |
298 |
298 |
299 |
Heating characteristics
|
|
|
|
HeatMaster 25 TC |
HeatMaster 35 TC |
HeatMaster 45 TC |
HeatMaster 70 TC |
HeatMaster 85 TC |
HeatMaster 120 TC |
Pre-heating time from 10 to 80°C (Heat source: boiler) |
min |
35 |
26 |
23 |
27 |
24 |
23 |
Reheat time from 40 to 90°C |
min |
30 |
28 |
25 |
37 |
36 |
30 |
Reheat time from 40 to 80°C |
min |
22 |
22 |
16 |
18 |
16 |
15 |
Heating time from 10 to 90°C |
min |
43 |
33 |
30 |
47 |
43 |
38 |
Combustion
|
|
|
|
HeatMaster 25 TC |
HeatMaster 35 TC |
HeatMaster 45 TC |
HeatMaster 70 TC |
HeatMaster 85 TC |
HeatMaster 120 TC |
Input max (heating) HCV |
kW |
27,8 |
38,9 |
50,0 |
77,6 |
94,4 |
127,7 |
Input max (heating) LCV |
kW |
25 |
35 |
45 |
69,9 |
85 |
115 |
Combustion efficiency |
% |
98,2 |
98,2 |
97,9 |
98,1 |
98 |
97,5 |
Efficiency at 30% load (EN677) |
% |
109,0 |
109,0 |
109,0 |
109,0 |
108 |
108 |
Efficiency at 100% load (50/30°C) |
% |
103,9 |
103,9 |
103,9 |
105,8 |
105,8 |
105,8 |
Efficiency (max output) 80/60°C |
% |
98 |
98 |
98 |
97,3 |
97 |
97 |
Efficiency (min output) 80/60°C |
% |
98 |
98 |
98 |
97,3 |
97,5 |
97,1 |
Efficiency DHW mode ΔT 30K |
% |
105,4 |
105,4 |
103,1 |
103,9 |
103,9 |
102,2 |
CO emissions max output |
ppm |
27 |
48 |
63 |
34 |
51 |
58 |
CO emissions min output |
ppm |
6 |
4 |
4 |
7 |
6 |
4 |
Mass rate of combustion products (gas) |
kg/h |
42 |
56 |
76 |
114 |
111 |
183 |
NOx weighted (GCV) (EN15502) |
mg/kWh |
24,6 |
29,5 |
33,2 |
33,1 |
29,3 |
31,1 |
NOx class (EN15502) |
|
6 |
6 |
6 |
6 |
6 |
6 |
Output power max (80/60°C) |
kW |
24,3 |
34,2 |
44,7 |
68,0 |
82,5 |
111,6 |
Output power min (80/60°C) |
kW |
4,9 |
6,8 |
8,8 |
20,9 |
20,5 |
24,3 |
Gas flow rate (min output) |
m³/h |
0,5 |
0,7 |
0,9 |
2,2 |
2,1 |
2,45 |
Domestic hot water performance
|
|
|
|
HeatMaster 25 TC |
HeatMaster 35 TC |
HeatMaster 45 TC |
HeatMaster 70 TC |
HeatMaster 85 TC |
HeatMaster 120 TC |
Peak flow at 40°C |
L/10’ |
361 |
408 |
451 |
716 |
783 |
900 |
Peak flow 1st hour at 40°C |
L/60’ |
1018 |
1328 |
1610 |
2455 |
2895 |
3620 |
Continuous flow at 40°C |
L/h |
788 |
1104 |
1390 |
2087 |
2534 |
3402 |
Peak flow at 45°C |
L/10’ |
301 |
339 |
373 |
592 |
646 |
676 |
Peak flow 1st hour at 45°C |
L/60’ |
865 |
1127 |
1366 |
2083 |
2456 |
3098 |
Continuous flow at 45°C |
L/h |
676 |
946 |
1192 |
1789 |
2172 |
2928 |
Peak flow at 60°C |
L/10’ |
183 |
197 |
224 |
348 |
371 |
440 |
Peak flow 1st hour at 60°C |
L/60’ |
577 |
749 |
894 |
1391 |
1638 |
1847 |
Continuous flow at 60°C |
L/h |
473 |
662 |
820 |
1252 |
1520 |
1754 |
Electrical Characteristics
|
|
|
|
HeatMaster 25 TC |
HeatMaster 35 TC |
HeatMaster 45 TC |
HeatMaster 70 TC |
HeatMaster 85 TC |
HeatMaster 120 TC |
Voltage |
V |
230 |
230 |
230 |
230 |
230 |
230 |
Frequency |
Hz |
50 |
50 |
50 |
50 |
50 |
50 |
Protection IP |
|
30 |
30 |
30 |
30 |
30 |
30 |
Electrical consumption |
W |
95 |
110 |
126 |
210 |
266 |
327 |
Electrical power requirements |
A |
0,7 |
0,8 |
0,85 |
1,4 |
1,7 |
2 |
Eco Design Fields
|
|
|
|
HeatMaster 25 TC |
HeatMaster 35 TC |
HeatMaster 45 TC |
HeatMaster 70 TC |
HeatMaster 85 TC |
HeatMaster 120 TC |
Space heating energy efficiency class |
|
A |
A |
A |
A |
A |
A |
Seasonal space heating efficiency (35°C) |
% |
93 |
93 |
93 |
93 |
92 |
92 |
Declared load profile |
|
XXL |
XXL |
XXL |
XXL |
XXL |
XXL |
Water heating energy efficiency class |
|
A |
A |
A |
A |
A |
A |
Water heating energy efficiency [ηwh] (EU 814/2013 Art 2 (15) Ann.IV-3) |
% |
87,2 |
87,2 |
87,2 |
85,0 |
85 |
85 |
Sound power level indoors LWA |
dB |
60 |
60 |
59 |
60 |
61 |
62 |
Cookies and Privacy
This website use cookies to ensure you get the best user experience on our website.