The store will not work correctly in the case when cookies are disabled.
ACV Heatmaster 45TC Condensing Boiler 05652301
Overview
ACV Heatmaster HM45TC Gas Fired Condensing Boiler 9.7-43.6Kw (No Flue) 5652301
HeatMaster 45 TC
Combined gas fired condensing boiler and water heater with stainless steel heat exchanger.
- 10-Year Heat Exchanger Warranty
- Tank-in-Tank
- BIM Objects
- Nat Gas and LPG
- Domestic and Commercial
- GAS
- BOILERS
- DHW PRODUCTION
- STANDARD
- CONCENTRIC
- FLOOR INSTALLATION
# GTIN : 5400891001479
# P/N : 05652301
ACV Heatmaster HM45TC Gas Fired Condensing Boiler 9.7-43.6Kw (No Flue) 5652301
- Heating and hot water from one unit saves space, reduces energy use and speeds up installation
- Operates in most efficient mode (condensing) for both heating and hot water
- Low maintenance with no anode protection required
- Reduces legionella risk due to temperature stored at > 60°C
- Corrosion-resistant stainless steel heat exchanger backed by a 10-year warranty reduces maintenance and increases system lifespan
- Suited to high demand and critical hot water premises such as hotels and hospitals
- Long life – 25-year guarantee on the corrosion resistant stainless steel cylinder
- Easy to use standardised controls using ACVMax control system
- Combine with Prestige® heat only boilers or Smart cylinder for highly efficient heating and hot water performance all from one manufacturer
- Suitable for vented or unvented systems (optional unvented kit required)
- Supplied with LPG kit for simple on-site conversion
|
HeatMaster 25 TC |
HeatMaster 35 TC |
HeatMaster 45 TC |
HeatMaster 70 TC |
HeatMaster 85 TC |
HeatMaster 120 TC |
Capacity (total) |
L |
196 |
196 |
196 |
315 |
315 |
315 |
Capacity (primary) |
L |
100 |
100 |
100 |
125 |
125 |
125 |
Capacity (domestic hot water) |
L |
96 |
96 |
96 |
190 |
190 |
190 |
Capacity expansion tank(s) |
L |
- |
- |
- |
- |
- |
- |
Chimney: Max pressure drop in flue pipe |
Pa |
130 |
130 |
130 |
150 |
150 |
170 |
Chimney: max length of concentric flue pipe |
m |
20 |
20 |
20 |
22 |
22 |
21 |
Chimney connection |
Ømm |
80/125 |
80/125 |
80/125 |
100/150 |
100/150 |
100/150 |
Connection - heating |
Ø" |
1 F |
1 F |
1 F |
1 ½ F |
1 ½ F |
1 ½ F |
Connection - DHW |
Ø" |
1 M |
1 M |
1 M |
1 M |
1 M |
1 M |
Connection gas |
Ø" |
3/4 M |
3/4 M |
3/4 M |
3/4 M |
3/4 M |
3/4 M |
Connection - safety valve |
Ø" |
1/2M |
1/2M |
1/2M |
1/2 M |
1/2 M |
1/2 M |
Max operating temperature |
°C |
87 |
87 |
87 |
87 |
87 |
87 |
Water pressure drop boiler at Δt = 20°C |
mbar |
3 |
6 |
10 |
9 |
14 |
27 |
Max service pressure heating (primary) |
bar |
3 |
3 |
3 |
3 |
3 |
3 |
Max service pressure (DHW) |
bar |
8,6 |
8,6 |
8,6 |
8,6 |
8,6 |
8,6 |
Height when tilted |
mm |
1855 |
1855 |
1855 |
2277 |
2277 |
2277 |
Weight (empty) |
kg |
177 |
177 |
177 |
298 |
298 |
299 |
Heating characteristics
|
|
|
|
HeatMaster 25 TC |
HeatMaster 35 TC |
HeatMaster 45 TC |
HeatMaster 70 TC |
HeatMaster 85 TC |
HeatMaster 120 TC |
Pre-heating time from 10 to 80°C (Heat source: boiler) |
min |
35 |
26 |
23 |
27 |
24 |
23 |
Reheat time from 40 to 90°C |
min |
30 |
28 |
25 |
37 |
36 |
30 |
Reheat time from 40 to 80°C |
min |
22 |
22 |
16 |
18 |
16 |
15 |
Heating time from 10 to 90°C |
min |
43 |
33 |
30 |
47 |
43 |
38 |
Combustion
|
|
|
|
HeatMaster 25 TC |
HeatMaster 35 TC |
HeatMaster 45 TC |
HeatMaster 70 TC |
HeatMaster 85 TC |
HeatMaster 120 TC |
Input max (heating) HCV |
kW |
27,8 |
38,9 |
50,0 |
77,6 |
94,4 |
127,7 |
Input max (heating) LCV |
kW |
25 |
35 |
45 |
69,9 |
85 |
115 |
Combustion efficiency |
% |
98,2 |
98,2 |
97,9 |
98,1 |
98 |
97,5 |
Efficiency at 30% load (EN677) |
% |
109,0 |
109,0 |
109,0 |
109,0 |
108 |
108 |
Efficiency at 100% load (50/30°C) |
% |
103,9 |
103,9 |
103,9 |
105,8 |
105,8 |
105,8 |
Efficiency (max output) 80/60°C |
% |
98 |
98 |
98 |
97,3 |
97 |
97 |
Efficiency (min output) 80/60°C |
% |
98 |
98 |
98 |
97,3 |
97,5 |
97,1 |
Efficiency DHW mode ΔT 30K |
% |
105,4 |
105,4 |
103,1 |
103,9 |
103,9 |
102,2 |
CO emissions max output |
ppm |
27 |
48 |
63 |
34 |
51 |
58 |
CO emissions min output |
ppm |
6 |
4 |
4 |
7 |
6 |
4 |
Mass rate of combustion products (gas) |
kg/h |
42 |
56 |
76 |
114 |
111 |
183 |
NOx weighted (GCV) (EN15502) |
mg/kWh |
24,6 |
29,5 |
33,2 |
33,1 |
29,3 |
31,1 |
NOx class (EN15502) |
|
6 |
6 |
6 |
6 |
6 |
6 |
Output power max (80/60°C) |
kW |
24,3 |
34,2 |
44,7 |
68,0 |
82,5 |
111,6 |
Output power min (80/60°C) |
kW |
4,9 |
6,8 |
8,8 |
20,9 |
20,5 |
24,3 |
Output power max (50/30°C) |
kW |
- |
- |
47,4 |
74,0 |
- |
121,7 |
Gas flow rate (min output) |
m³/h |
0,5 |
0,7 |
0,9 |
2,2 |
2,1 |
2,45 |
Domestic hot water performance
|
|
|
|
HeatMaster 25 TC |
HeatMaster 35 TC |
HeatMaster 45 TC |
HeatMaster 70 TC |
HeatMaster 85 TC |
HeatMaster 120 TC |
Peak flow at 40°C |
L/10’ |
361 |
408 |
451 |
716 |
783 |
900 |
Peak flow 1st hour at 40°C |
L/60’ |
1018 |
1328 |
1610 |
2455 |
2895 |
3620 |
Continuous flow at 40°C |
L/h |
788 |
1104 |
1390 |
2087 |
2534 |
3402 |
Peak flow at 45°C |
L/10’ |
301 |
339 |
373 |
592 |
646 |
676 |
Peak flow 1st hour at 45°C |
L/60’ |
865 |
1127 |
1366 |
2083 |
2456 |
3098 |
Continuous flow at 45°C |
L/h |
676 |
946 |
1192 |
1789 |
2172 |
2928 |
Peak flow at 60°C |
L/10’ |
183 |
197 |
224 |
348 |
371 |
440 |
Peak flow 1st hour at 60°C |
L/60’ |
577 |
749 |
894 |
1391 |
1638 |
1847 |
Continuous flow at 60°C |
L/h |
473 |
662 |
820 |
1252 |
1520 |
1754 |
Electrical Characteristics
|
|
|
|
HeatMaster 25 TC |
HeatMaster 35 TC |
HeatMaster 45 TC |
HeatMaster 70 TC |
HeatMaster 85 TC |
HeatMaster 120 TC |
Voltage |
V |
230 |
230 |
230 |
230 |
230 |
230 |
Frequency |
Hz |
50 |
50 |
50 |
50 |
50 |
50 |
Protection IP |
|
30 |
30 |
30 |
30 |
30 |
30 |
Electrical consumption |
W |
95 |
110 |
126 |
210 |
266 |
327 |
Electrical power requirements |
A |
0,7 |
0,8 |
0,85 |
1,4 |
1,7 |
2 |
Eco Design Fields
|
|
|
|
HeatMaster 25 TC |
HeatMaster 35 TC |
HeatMaster 45 TC |
HeatMaster 70 TC |
HeatMaster 85 TC |
HeatMaster 120 TC |
Space heating energy efficiency class |
|
A |
A |
A |
A |
A |
A |
Seasonal space heating efficiency (35°C) |
% |
93 |
93 |
93 |
93 |
92 |
92 |
Declared load profile |
|
XXL |
XXL |
XXL |
XXL |
XXL |
XXL |
Water heating energy efficiency class |
|
A |
A |
A |
A |
A |
A |
Water heating energy efficiency [ηwh] (EU 814/2013 Art 2 (15) Ann.IV-3) |
% |
87,2 |
87,2 |
87,2 |
85,0 |
85 |
85 |
Sound power level indoors LWA |
dB |
60 |
60 |
59 |
60 |
61 |
62 |
Energy Label |
|
|
|
|
|
- |
- |
Product Fiche |
|
|
|
|
|
|
|
Cookies and Privacy
This website use cookies to ensure you get the best user experience on our website.